By opening the real-time diagnostics window while connected to a live panel, you can view the exact analogue return values of your detectors.
Verdict: For a single-device label change, the front panel is fine. For commissioning, troubleshooting, or full system programming,
Beyond commissioning, the software is a powerful tool for fault finding and ongoing system maintenance. During the commissioning process (often a "soak period"), engineers can use the software to help locate problematic devices. If a connection to a panel is made using the "Connect" screen of Loop Explorer Version 3 (or later), it is possible to transfer analogue levels, zero calibration, and fire calibration points for each detection device. This data can be saved into a comma-separated values (CSV) file for later detailed analysis, helping to identify devices that are drifting out of calibration or are excessively dirty.
In Loop Explorer, click or select the correct COM port from the communications menu. Select Write to Panel (Upload configuration). Kentec Syncro - Loop Explorer Software
The panel logs “Device Missing” for an address, but it reappears after a reset. Solution: Open Loop Explorer and watch the Device Health History graph for that address. You will see dips in the loop current. If the dip coincides with a specific time (e.g., a door closing nearby), you likely have a loose termination in that device’s base.
Note: Configuration files are not always seamlessly interchangeable between LE1 and LE2, so engineers must ensure they are using the software version that aligns with the specific generation of hardware installed on site. Best Practices for Using Loop Explorer
Apply timing delays if staging evacuation (e.g., Stage 1 warning tone vs. Stage 2 continuous evacuation tone). Step 6: Transferring Data to the Panel By opening the real-time diagnostics window while connected
(and its successor, Loop Explorer 2 ) is a professional software suite developed by Kentec Electronics to program, configure, and manage their range of analogue addressable fire control panels, including the Syncro and Syncro AS series. Key Functions & Capabilities Loop Explorer 2 User Guide
The engineer starts by creating a "blank project" in Loop Explorer or opening an existing one. Using the graphical interface, devices are added to detection loops, each assigned a unique address. Device attributes, such as zone allocations and location messages, are configured. The software's comprehensive cause and effect logic is then built by combining inputs (e.g., smoke detectors, call points) to operate on outputs (e.g., sounders, relays, plant control modules).
The software provides a visual, intuitive interface to build, edit, and upload complex site configurations. Instead of programming a multi-panel network manually through a small panel keypad, technicians can map out an entire building’s fire infrastructure on a laptop and transfer the data in seconds. Key Features and Capabilities 1. Visual Device Mapping During the commissioning process (often a "soak period"),
Allows for easy zone management, device labeling, and property changes.
After successful testing, the final "as-built" configuration file is downloaded back to the laptop, backed up to secure cloud storage, and printed for the client's operation and maintenance (O&M) manual. Loop Explorer 1 vs. Loop Explorer 2
The software is designed with a . Users can switch between different views—such as the Loop View (linear representation of the wiring loop), the Graphic View (floor plans), and the Event Log.