The software is packed with tools designed to reduce on-site labor and improve system reliability: Offline Configuration:
In recognition of its global user base, XtraLis VSC includes . Users can configure and maintain the system in their native language, and the software can automatically translate data files for viewing in another language by a colleague. Furthermore, the interface is customizable , offering multiple views for full network management. For example, a user could simultaneously display an overview of the entire network, a real-time event list, and a mimic diagram of a specific detector.
The software acts as a centralized command center for aspirating smoke detection (ASD) networks. It replaces manual hardware adjustments with a streamlined digital interface. xtralis vsc software
Allow the installer to install the Xtralis USB device drivers. These are critical for the software to recognize VESDA-E units via a direct USB connection.
Solution: Ping the detector's IP address from your command prompt. Ensure that your firewall permits VSC traffic and verify that ports 5000 and 5001 are open if communicating across corporate networks. Cause: Insufficient user login privileges. The software is packed with tools designed to
VSC reports detailed diagnostic data, including:
The VLI is a robust aspirating smoke detector designed for harsh industrial environments. XtraLis VSC is the primary interface for: For example, a user could simultaneously display an
Set specific obscuration levels (% obs/m or % obs/ft) for Alert, Action, Fire 1, and Fire 2 alarm stages.
Xtralis VSC is compatible with various generations of hardware, including: : VEP, VEU, VEA, and VES. Legacy VESDA : VLP, VLS, VLC, and VLF.